- Engineering Step-by-Step
- Connectivity
- BACnet
- BACnet Driver
- Configuring the BT BACnet Stack
Configuring the BT BACnet Stack
- System Manager is in Engineering mode.
- A BACnet driver has been added and started.
- In System Browser, select Management View.
- Depending on where the BACnet Driver is located (Desigo CC server or FEP station), select one of the following:
- Project > Management System > Servers > Main Server > Drivers
- Project > Management System > FEPs > [FEP station] > Drivers
- Click the BACnet tab.
- Open the BT BACnet Stack Config expander.
- In the BT BACnet Stack Gateway Port Table section, click Add and then select BACnet/IP or Ethernet.
- In the Port Properties expander, set the Network Number where your management station is connected (typically =1).
- Leave the Attached check box selected if you want the router port attached and accessible to other devices on the BACnet network.
- In the Adapter drop-down list, select the hardware adapter this driver will be using.
- Accept the default IP address and UDP Port settings.
- (Optional) To add a Virtual Port, click Add and then select Virtual.
- (Optional) Configure the Physical Port as BBMD or Foreign Device.
- Click Save
.