Configuring the BT BACnet Stack

  • System Manager is in Engineering mode.
  • A BACnet driver has been added and started.
  1. In System Browser, select Management View.
  1. Depending on where the BACnet Driver is located (Desigo CC server or FEP station), select one of the following:
  • Project > Management System > Servers > Main Server > Drivers
  • Project > Management System > FEPs > [FEP station] > Drivers
  1. Click the BACnet tab.
  1. Open the BT BACnet Stack Config expander.
  1. In the BT BACnet Stack Gateway Port Table section, click Add and then select BACnet/IP or Ethernet.
  1. In the Port Properties expander, set the Network Number where your management station is connected (typically =1).
  1. Leave the Attached check box selected if you want the router port attached and accessible to other devices on the BACnet network.
  1. In the Adapter drop-down list, select the hardware adapter this driver will be using.
  1. Accept the default IP address and UDP Port settings.
  1. (Optional) To add a Virtual Port, click Add and then select Virtual.
  1. (Optional) Configure the Physical Port as BBMD or Foreign Device.
  1. Click Save .