- Engineering Reference
- Subsystem Integration
- SPC
- SPC System Limits and Compatibility
SPC System Limits and Compatibility
System limits
- 50 SPC panels or 5000 SPC points per SPC driver
- 5 SPC drivers on server/FEP
Compatibility information
- Panel versions:
- SPC V3.6.5/3.6.6 via EDP/FlexC
- SPC V3.7.1 via FlexC
- SPC V3.8.5 via FlexC
- SPC V3.8.6 via FlexC
- SPC V3.9 via FlexC
Limitations and Known Issues
- When the SPC panels are connected via FlexC, the status of SPC users cannot be properly shown by the management station. Users are erroneously reported as
Isolated and the status of Logged-in is missing.
Related Topics