- Engineering Reference
- Subsystem Integration
- CS1140 AlgoRex Fire
- AlgoRex CS11 System Limits and Compatibility
AlgoRex CS11 System Limits and Compatibility
System Limits
- 1 NK823x per BACnet network
- Up to 4 downstream connections per NK823x, on the 5 possible communication lines: the 4 COM ports and the I2C line for DF8000. A configuration including all five connections is not supported.
- Max. 50 subsystems (CC11, CI11, CK11, STT11, STT20, SI400 Sintony, DF8000) per NK823x
- Max. 16 C-Bus stations (CT11, CC11, CI11, CK11) per AlgoRex fire system
- Max. 2 CK11 gateways per AlgoRex fire system (8 CC11/CI11 panels per CK11)
- Max. 25,000 objects (~10,000 physical points) per NK823x
Compatibility Information
- Panel versions (FW / tool version): EP7F-SR2 (FW 7.39 / AlgoWorks V1.37), Z1 (FW 7.76 / AlgoWorks V1.46), Z2.1 (FW 7.38 / AlgoWorks V1.50), Z2.2 (FW 7.92 & 8.03 / AlgoWorks V1.63), Z3 (FW 8.31 / AlgoWorks 1.92A), Z4 (FW 8.31 / AlgoWorks V1.92A), EP7F-SR3 (FW 8.3x / AlgoWorks V1.94).