SiPass Auxiliary Objects Commands

The section presents a description of the SiPass auxiliary objects (inputs/outputs) and the related control commands available from the Desigo CC management station. These inputs/outputs can be used to connect optional external devices such as buzzers, horn, lights, and elevators. For UL/ULC Access Control compliance information, see Notice for UL/ULC Norms Compliance.

SiPass Auxiliary Input Commands

The following table shows and explains the available input commands.

Door Command

Description

Disable

Permanently excludes the input from the system. This command overrides the programmed enable/disable schedule that may be defined in the SiPass configuration.

Enable

Permanently includes the input in the system. This command overrides the programmed enable/disable schedule that may be defined in the SiPass configuration.

Cancel PA

Cancels the Permanent Action (PA) of manual Enable or Disable. This command does not change the current input status, but removes the permanent effect of the latest Enable/Disable command. This allows a subsequent programmed action to complete successfully.

Return to AC

Returns to Access Control (AC) the input control with immediate effect. This command cancels the latest Enable/Disable command and results in the input status being updated as necessary to reflect the current programmed schedule.

 

SiPass Auxiliary Output Commands

The following table shows and explains the available output commands.

Door Command

Description

Secure

Permanently sets the relay output to the secure state (default condition, which can be configured as normally open or normally closed). This command overrides the programmed secure/unsecure schedule that may be defined in the SiPass configuration.

Unsecure

Permanently sets the relay output to the unsecure state (as opposite to the configured secure state). This command overrides the programmed secure/unsecure schedule that may be defined in the SiPass configuration.

Allow Access

Temporarily sets the relay output to the unsecure state to allow an access. The activation delay is programmed in the SiPass configuration.

Allow Access > Cancel PA

Cancels the Permanent Action (PA) of manual Secure or Unsecure. This command does not change the current output status, but removes the permanent effect of the latest Secure/Unsecure command. This allows a subsequent programmed action to complete successfully.

Allow Access > Return to AC

Returns to Access Control (AC) the output control with immediate effect. This command cancels the latest Secure/Unsecure command and results in the output status being updated as necessary to reflect the current programmed schedule.

Allow Access > Single Pulse

Set the relay output to the unsecure state for 3 sec, and then back to secure.

Allow Access > Toggle

Inverts the status of the relay output.

Lock

Sets the relay output to the secure state for a specified a period of time (hhh:mm:ss).

Unlock

Sets the relay output to the unsecure state for a specified a period of time (hhh:mm:ss).

Fast Pulse

Sends out a series of high-frequency pulses (1-sec period) for a specified period of time (hhh:mm:ss).

Slow Pulse

Sends out a series of low-frequency pulses (2-sec period) for a specified period of time (hhh:mm:ss).